Buying a Small Ontario Plaza? The Fire Code Part 6 Records the Seller Should Be Able to Hand You

By , Broker, RE/MAX Realtron Realty Inc. (About Ming) · Published

Ming Ren · Broker · RE/MAX Realtron Realty Inc., Brokerage

← All articles · Commercial Real Estate & Leasing · Category guide

I am Ming Ren, a Broker with RE/MAX Realtron.

The conclusion first: during a conditional period you cannot pressure-test a sprinkler system or run a full fire alarm test yourself. What you can test is the paper. Ontario's Fire Code (O. Reg. 213/07) is built on a simple logic: every check, test and maintenance task the Code requires must produce a written record; records are kept at the building for at least two years, with at least the most recent and the immediately preceding record of each test retained. A seller who can hand over that file is a seller whose building has been maintained. Every gap in the file is cost and risk that transfers to you on closing.

Who is responsible: the Code's "owner" means whoever has control

Division A of the Fire Code defines "owner" as any person, firm or corporation having control over any portion of the building or property, and Division B places responsibility for carrying out the Code on the owner unless otherwise specified. In a small plaza that splits along control lines: the landlord controls common areas and building systems, tenants control what sits inside their units — and the lease should say so expressly. In due diligence, get that responsibility map first; it tells you whose records to ask for, system by system.

The general records rule sits in Division B 1.1.2: when a required test, corrective measure or operational procedure is performed, a written record is prepared noting what was done and when; copies are retained at the building for at least two years, keeping at least the latest and previous record of each test; and initial verification or test reports for systems installed after November 21, 2007 are kept for the life of the system. Every line below sits on that foundation.

System by system: the Part 6 checklist

Part 6 of Division B governs the installation, checking, inspection, testing, maintenance and operation of fire protection equipment. Work through it by system:

System Required rhythm (headline) Paper that should exist
Portable extinguishers (s.6.2) Inspected monthly; maintained to NFPA 10 A service tag on each extinguisher, or approved alternative records
Fire alarm (s.6.3) Checked, inspected and tested to CAN/ULC-S536, with the annual test at its core; control facility checked daily Device-by-device test records, current system description, technician qualification records
Sprinklers and standpipes (ss.6.4–6.5 area) Weekly gauge checks; further checks on the NFPA 25 or Code-specified monthly/annual rhythm An inspection record for each system
Emergency lighting and exit signs (s.6.7 area) Monthly and annual checks and tests Test records

Treat this table as an outline, not the Code: each system carries detailed items, and the current Code text governs. The method is the point — never ask a seller "fire is all fine, right?" Ask, system by system, "where are the last two records for this one?" The item nobody can produce is the gap.

Price the gaps properly. A lapsed extinguisher record is cheap to cure. A missing annual fire alarm test report means paying a qualified firm to test from scratch, plus whatever repairs the test uncovers. A sprinkler system with no history makes your first annual inspection a blind draw. Record each gap in the due diligence report under two columns — cost to restore records, and a reserve for repairs — not as a single vague note that "fire is to be confirmed."

After closing: records stay with the building, duties follow control

Records are required to be kept at the building, so they should pass as part of the property file on closing; a buyer can require delivery of existing fire records, service contracts and testing-company details expressly in the agreement. On closing day, do two things: inventory the file against the two-year / last-two-records rule, and calendar every system's next due date — the Code's rhythm does not restart because ownership changed. On the tenant side, mirror the split in the leases: in-unit extinguishers and kitchen suppression systems carry tenant maintenance and record duties in writing, so an inspection never turns into the landlord and tenant pointing at each other.

An invented example: a ten-unit plaza where the seller's "Fire" folder holds a single sprinkler contractor invoice. Run the table and the gaps appear — two extinguishers with expired tags, no CAN/ULC-S536 annual test record for the alarm, no monthly emergency-lighting records. The building is not unbuyable; the buyer prices the re-testing and likely repairs into the conditions and requires delivery of the records in the agreement. Rhythms and costs in a real case follow the Code text and the local fire department's requirements.

Three misunderstandings I hear most often

"The fire department inspected last year and it was fine, so we're compliant." Passing a spot inspection is not the same as having the records. The Code requires an ongoing rhythm of checks and tests, each documented. A buyer needs the paper that proves the rhythm, not an impression from one visit.

"The equipment looks new, so it must be fine." Condition is judged by records, not appearance. An untested "new" device is, to the Code, an untested device — and faults are found by testing, not by looking.

"Fire is the tenants' problem, not the landlord's." Responsibility follows control. Building systems and landlord-controlled areas sit with the landlord; if the lease does not allocate duties and nobody collects records, an inspector starts with the property's owner.

My due diligence order

  1. Get the system inventory first: exactly which fire protection systems this building has, confirmed one by one, including kitchen suppression and generator-related items.
  2. Request records system by system: the last two years, the latest and previous record of each test, plus initial verification reports for newer systems.
  3. Align the responsibility map with the leases: who maintains each system today, whose name the service contracts are in, and every expiry date.
  4. Price each gap: re-testing cost plus a repair reserve, written into the due diligence conclusion and the price negotiation.
  5. List the closing deliverables in the agreement — fire records, service contracts, testing-company contacts — and re-calendar every test date immediately after closing.

Trust Professional, Diligent Work. I am Ming Ren. On a commercial purchase, fire safety gets checked system by system against the records — never on a "should be fine."


This article is general information only, not legal or fire engineering advice. Exact rhythms follow the current Fire Code text and local fire department requirements. Consult an Ontario fire protection consultant or lawyer before acting.

Primary sources: Ontario Fire Code, O. Reg. 213/07, Division A 1.4.1.2, Division B 1.1.2 and Part 6 (Ontario e-Laws, consulted November 2026). The ten-unit plaza example is illustrative only.